Experimental study on transient behavior of semi-open two-phase thermosyphon

Abstract: An experimental system was set up to measure the temperature, pressure, heat transfer rate and mass flow rate in a semi-open two-phase thermosyphon. The behaviors of a semi-open two-phase thermosyphon during startup, shutdown and lack of water were studied to get complete understanding of its thermal characteristics. The variation of wall temperature, heat-exchange condition and pressure fluctuations of semi-open two-phase thermosyphons showed that the startup of SOTPT needs about 60~70 min; the startup speed of SOTPT is determined by the startup speed of the condensation section; the average pressure in the heat pipe is equal to the environmental pressure usually; the shutdown of SOTPT needs about 30~50 min; a semi-open two-phase thermosyphon has good response to lack of water accident.

Key words: Semi-open two-phase thermosyphon (SOTPT), Transient heat transfer, Startup, Lack of water, Shutdown


Share this article to: More

Go to Contents

References:

<Show All>

Open peer comments: Debate/Discuss/Question/Opinion

<1>

Please provide your name, email address and a comment





DOI:

10.1631/jzus.2004.1565

CLC number:

TK172.4

Download Full Text:

Click Here

Downloaded:

3189

Clicked:

6475

Cited:

2

On-line Access:

Received:

2004-01-07

Revision Accepted:

2004-04-15

Crosschecked:

Journal of Zhejiang University-SCIENCE, 38 Zheda Road, Hangzhou 310027, China
Tel: +86-571-87952276; Fax: +86-571-87952331; E-mail: jzus@zju.edu.cn
Copyright © 2000~ Journal of Zhejiang University-SCIENCE