Improved direct power control of a grid-connected voltage source converter during network unbalance

Abstract: This paper deals with an improved direct power control (DPC) strategy for the pulse width modulation (PWM) voltage source converter (VSC) under unbalanced grid voltage conditions. In order to provide enhanced control performance for the VSC, the resonant controllers tuned at the double grid frequency are applied in the DPC design to eliminate the power pulsations and dc link voltage ripples produced by the transient unbalanced grid faults. In this way, the output power and dc link voltage of the VSC can be directly regulated without positive and negative sequential decomposition. As a result, and as has been verified by experiment, the proposed method can provide fast dynamic response with easy implementation.

Key words: Voltage source converter, Direct power control, Unbalance, Resonant controller


Share this article to: More

Go to Contents

References:

<Show All>

Open peer comments: Debate/Discuss/Question/Opinion

<1>

Please provide your name, email address and a comment





DOI:

10.1631/jzus.C0910702

CLC number:

TM314; TM614

Download Full Text:

Click Here

Downloaded:

3370

Clicked:

7921

Cited:

4

On-line Access:

2010-09-30

Received:

2009-11-14

Revision Accepted:

2010-01-29

Crosschecked:

2010-09-03

Journal of Zhejiang University-SCIENCE, 38 Zheda Road, Hangzhou 310027, China
Tel: +86-571-87952276; Fax: +86-571-87952331; E-mail: jzus@zju.edu.cn
Copyright © 2000~ Journal of Zhejiang University-SCIENCE