|
Frontiers of Information Technology & Electronic Engineering
ISSN 2095-9184 (print), ISSN 2095-9230 (online)
2015 Vol.16 No.4 P.321-334
Multiple target implementation for a doubly fed induction generator based on direct power control under unbalanced and distorted grid voltage
Abstract: This paper presents a multiple target implementation technique for a doubly fed induction generator (DFIG) under unbalanced and distorted grid voltage based on direct power control (DPC). Based on the mathematical model of DFIG under unbalanced and distorted voltage, the proportional and integral (PI) regulator is adopted to regulate the DFIG average active and reactive powers, while the vector PI (VPI) resonant regulator is used to achieve three alternative control targets: (1) balanced and sinusoidal stator current; (2) smooth instantaneous stator active and reactive powers; (3) smooth electromagnetic torque and instantaneous stator reactive power. The major advantage of the proposed control strategy over the conventional method is that neither negative and harmonic sequence decomposition of grid voltage nor complicated control reference calculation is required. The insensitivity of the proposed control strategy to DFIG parameter deviation is analyzed. Finally, the DFIG experimental system is developed to validate the availability of the proposed DPC strategy under unbalanced and distorted grid voltage.
Key words: Direct power control, Doubly fed induction generator, Unbalanced and distorted grid voltage, Vector proportional and integral resonant regulator, Parameter deviation
创新点:采用的直接目标控制策略,无需对定子电压或电流分量进行负序及谐波分量提取,此外,也无需对各个控制目标进行参考值计算,因此能够简化控制策略结构,有利于控制系统快速动态响应能力。
方法:首先,简述双馈风力发电机组在不平衡及谐波畸变电网条件下的数学模型。然后,提出此条件下的直接目标控制策略,分别直接对三个目标中的待控制分量进行调节,其中PI调节器确保DFIG输出有功功率及无功功率的平均值,而VPI调节器确保实现三个控制目标中的任意一个。此外,当实现控制目标定子输出有功功率及无功功率平稳时,对定子电流中的三次谐波分量进行理论角度的定量分析;且对所提基于VPI调节器的闭环控制进行针对DFIG电机参数偏移的鲁棒性分析。最终,通过MATLAB/Simulink进行仿真分析验证,并搭建实验硬件平台系统进行实验验证,最终证明所提控制策略的有效性与可行性。
结论:提出改善运行于不平衡及谐波电网下的双馈风力发电机组运行性能的控制策略,所采用的三个控制目标分别为DFIG输出定子电流三相对称且正弦、DFIG输出定子有功功率及无功功率平稳和DFIG电磁转矩与输出无功功率平稳。所提控制策略相比于传统控制策略具有如下优点:无需对定子电压或电流进行负序及谐波分量提取且无需对各个控制目标进行参考值计算。
关键词组:
References:
Open peer comments: Debate/Discuss/Question/Opinion
<1>
DOI:
10.1631/FITEE.1400170
CLC number:
TM315
Download Full Text:
Downloaded:
3400
Download summary:
<Click Here>Downloaded:
2109Clicked:
7676
Cited:
0
On-line Access:
2024-08-27
Received:
2023-10-17
Revision Accepted:
2024-05-08
Crosschecked:
2015-03-06